Non-Wetted Electrode Electromagnetic Flow Sensors

FD-M series

Catalogues View Catalogue

Amplifier Unit, DIN Rail Mount Type, Main Unit, PNP FD-MA1AP

FD-MA1AP - Amplifier Unit, DIN Rail Mount Type, Main Unit, PNP

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Data Sheet (PDF)

Manuals

CAD Data

360°view (3D PDF)

  • CE Marking
  • UL Recognition(c/us)

Specifications

Model

FD-MA1AP*1

Type

DIN mounted*2 (Main unit)

Rated flow range

FD-MH10A : 0.5 to 10L/min, FD-MH50A : 2.5 to 50L/min, FD-MH100A : 5 to 100L/min, FD-MH500A : 25 to 500L/minThe rated flow range indicates the range that is supposed to be used in general.*3

Possible display range

FD-MH10A : 0.5 to 20L/min, FD-MH50A : 2.5 to 100L/min, FD-MH100A : 5 to 200L/min, FD-MH500A : 25 to 1000L/min*4

Possible ranges to set

FD-MH10A : 0 to 20 L/min,FD-MH50A : 0 to 100 L/min,FD-MH100A : 0 to 200 L/min,FD-MH500A : 0-999.9 L/min

Zero-cut flow rate

FD-MH10A : 0.5L/min, FD-MH50A : 2.5L/min, FD-MH100A : 5L/min, FD-MH500A : 25L/min*4

Display power

Dual row display with 4-digit, 7 segment LED, other indicators

Display resolution

FD-MH10A: 0.01/0.1 (L/min) selectable, FD-MH50A: 0.1/1 (L/min) selectable, FD-MH100A: 0.1/1 (L/min) selectable, FD-MH500A: 0.1/1 (L/min) selectable

Repeatability

0.5 s : ±5% of F.S.,1 s : ±3.5% of F.S., 2.5 s : ±2.5% of F.S., 5 s : ±1.6% of F.S., 10 s : ±1% of F.S., 30 s : ±0.8% of F.S., 60 s : ±0.6% of F.S.*5

Hysteresis

Variable

Response time (chatter prevention feature)

500 ms/1 s/2.5 s/5 s/10 s/30 s/60 s variable

Accumulated flow unit

FD-MH10A : 0.01/0.1/1/10/100 (ℓ) selectable,FD-MH50A : 0.1/1/10/100/1000 (ℓ) selectable,FD-MH100A : 0.1/1/10/100/1000 (ℓ) selectable,FD-MH500A : 1/10/100/1000/10000 (ℓ) selectable

Accumulation data storage cycle

Save to memory every 10 seconds

Memory backup

EEPROM (Data storage length : min. 10 years, Data read/write frequency : min. 1 million times)

Control output

Maximum PNP open-collector output : 100 mA/ch*6 (30 V or less)

Analogue output

4-20 mA, max. load resistance 260Ω, Analogue output range can be set to any value

Integration reset/bank switch input/flow zero function input

|input time : 20 ms or greater, Either accumulation reset or bank switching mode can be selected

Power/current consumption

Normal : 1700 mW (70 mA), Power save : 1440 mW (60 mA)

Rating

Power voltage

24 VDC, Ripple (P-P) 10 % or less

Environmental resistance

Ambient temperature

0 to +50 °C (No freezing)

Relative humidity

35 to 85 % RH (No condensation)

Vibration resistance

10 to 55 Hz, Double amplitude 1.5 mm, 2 hours in each of the X, Y, and Z directions

Material

Main case : polycarbonate, Key tops : polyacetal, Front sheet : polycarbonate, Cable : PVC

Accessories

instruction manual

Weight

Approx. 115 g

*1 The models with “A” at the end of the name have additional functions such as display averaging. Use the head with “A” at the end of the name. When connecting conventional heads without “A” at the end, the FD-MH operates in the same way
as the conventional models.
*2 Only connect to the back of DL-RS1 (A) or FD-MA.
*3 The rated flow range indicates recommended operating range.
*4 Flow under the zero cut flow will be displayed as 0 L/min.
*5 Convert the F.S. (full scale) listed in the table according to the rated flow range.
*6 Maximum 20 mA for alarm output. When the total number of extension units is between 6 and 10, set each output current to 10 mA or less.

Data Sheet (PDF) Other Models