Compact Switching Power Supply
MS2 series
Specs Compact Switching Power Supply MS2 series
Model |
MS2-H50 |
MS2-H75 |
MS2-H100 |
MS2-H150 |
MS2-H300 |
|||
Image |
|
|
|
|
|
|||
Input conditions |
Input voltage |
85 to 264 VAC, 110 to 370 VDC*1 |
||||||
Frequency |
47 to 63 Hz, DC*1 |
|||||||
Inputconditions |
Input current (100/200 VAC) |
1.3/0.7A or less |
1.9/0.9A or less |
2.1/1.3A or less |
2.2/1.1A or less |
3.9/1.8A or less |
||
Efficiency (100/200 VAC) |
82/85% typ. (with 100% load) |
|||||||
Leakage current (100/200 VAC) |
0.4/0.75 mA max. (with 100% load) |
|||||||
Rush current (100/200 VAC) |
25/50 A max. (with 100% load, at 25°C cold start) |
18/36A max. |
||||||
Output characteristics |
Rated voltage |
24V |
||||||
Variable voltage range |
±5% (with V.ADJ) |
|||||||
Rated current |
2.1A (Class2) |
3.2A |
4.5A |
6.5A |
12.5A |
|||
Ripple/noise voltage |
180mV (p-p) or less |
|||||||
Input fluctuation |
0.4% or less |
|||||||
Load fluctuation |
1.5% or less |
|||||||
Temperature fluctuation |
0.02 %/ ºC max. |
|||||||
Startup time |
500 ms max. (at Surrounding Air Temperature of 0 to 55°C under I/O rated conditions) |
|||||||
Output holding time |
20 ms min. (at Surrounding Air Temperature of 25°C under I/O rated conditions) |
|||||||
Protection |
Overcurrent protection |
Activates when the current reaches 125% or more of the rated output current. Constant current voltage limiting. Automatic reset 2.7 A min. |
Activates when the current reaches 125% or more of the rated output current. Constant current voltage limiting. Automatic reset 4.0 A min. |
Activates when the current reaches 125% or more of the rated output current. Constant current voltage limiting. Automatic reset 5.3 A min. |
Activates when the current reaches 125% or more of the rated output current. Constant current voltage limiting. Automatic reset 7.9 A min. |
Activates when the current reaches 125% or more of the rated output current. Constant current voltage limiting. Automatic reset 15.6 A min. |
||
Overvoltage protection |
Activates when the voltage reaches 26.4 V or more. Voltage turn-off. Operation resumes when the input power isturned on again.*2 |
|||||||
Display |
Display power |
3-digit, 7-segment LED (Character height: 10 mm) |
||||||
Power off memory time |
Approx. 10 years (at 20°C) |
|||||||
Display resolution |
0.1A/0.4V /1% |
|||||||
Applicable standards |
Safety standards |
UL508, UL60950-1 |
||||||
EMC standard |
FCC Part15B Class A, EN55011 Class A, EN61000-6-2 |
|||||||
Limits for harmonic current emissions |
EN61000-3-2*3 |
|||||||
Other |
Parallel operation |
Possible (OP-42207 is required.)*4 |
||||||
Series operation |
Possible (External diode is required.)*4 |
|||||||
Cooling method |
Natural air-cooling |
|||||||
Environmental resistance |
Insulation resistance |
100 MΩ min. (with 500 VDC megohmmeter) |
||||||
Ambient temperature |
-10 to +55 °C (No freezing) (See "Output conditions".) |
|||||||
Storage temperature |
-20 to +70 °C (No freezing) |
|||||||
Relative humidity |
25 to 85 % RH (No condensation) |
|||||||
Withstand voltage |
3.0 kVAC, 50/60 Hz, 1 min (across input and output terminals) |
|||||||
Vibration resistance |
10 to 57 Hz, Double amplitude 0.3 mm, 57 to 500 Hz, 19.6 m/s2 (2 G), 5.5-minute cycle, 2 hours in each of the X, Y, and Z directions |
|||||||
Shock resistance |
Peak acceleration: 300 m/s2, 2 times in each of the X, Y, and Z directions |
|||||||
Weight |
Approx. 270 g |
Approx. 470 g |
Approx. 490 g |
Approx. 700 g |
Approx. 1,540 g |
|||
*1 The rated input voltage and rated frequency when applying for safety standards are 100 to 240 VAC, 50/60 Hz. |