Non-Wetted Electrode Electromagnetic Flow Sensors
FD-M series
Recommended Replaceable Products: Main Unit, Landscape, 10 L/min, PNP - FD-M10AYP
Contact Us: 1-888-539-3623 Enquiry form
Main Unit, Landscape, 10 L/min, PNP FD-M10YP
*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.
Specifications
Model | FD-M10YP | |||
Type | For horizontal piping | |||
Output | PNP output | |||
Shape | Built-in amplifier | |||
Rated flow range | 0.5 to 10 L/min*1*2 | |||
Possible display range | 0.5 to 30 L/min*3 | |||
Possible ranges to set | 0 to 30 L/min | |||
Zero-cut flow rate | 0.5 L/min*4 | |||
Connection diameter | Rc3/8 (10A) | |||
Allowable fluid | Water or non-corrosive fluid | |||
Conductivity of detection fluids | 5 µS/cm or higher | |||
Detection fluid temperature | 0 to +85°C (No freezing) | |||
Pressure loss | 0.01 MPa or less | |||
Display power | Dual row display with 4-digit 7-segment LED, bar display (2 colours) | |||
Display resolution | 0.01/0.1 (L/min) selectable | |||
Repeatability | 0.5 s : ±5% of F.S., 1 s : ±3.5% of F.S., 2.5 s : ±2.5% of F.S., 5 s : ±1.6% of F.S., 10 s : ±1% of F.S., 30 s : ±0.8% of F.S., 60 s : ±0.6% of FS.*5 | |||
Hysteresis | Variable | |||
Response time (chatter prevention feature) | 500 ms/1 s/2.5 s/5 s/10 s/30 s/60 s variable | |||
Accumulated flow unit | Selectable from 0.01/ 0.1 / 1 / 10 /100 (L) | |||
Accumulation data storage cycle | Save to memory every 10 seconds | |||
Memory backup | EEPROM (Data storage length : min. 10 years, Data read/write frequency : min. 1 million times) | |||
Control output | Maximum PNP open-collector output : 100 mA/ch*6 (30 V or less) | |||
integration pulse output | Residual voltage : 1 V or less | |||
Analogue output | 4 to 20 mA, maximum load resistance 260 Ω Analogue output range can be set arbitrary | |||
Abnormality alarm output | Three outputs (N.O./N.C. switchable) | |||
Integration reset/bank switch input/flow zero function input | Selectable from 2 types, input time : 20 ms or more | |||
Power/current consumption | Normal : 1700 mW (70 mA), Power save : 1000 mW (40 mA) | |||
Rating | Power voltage | 24 VDC, Ripple (P-P) 10 % or less | ||
Environmental resistance | Enclosure rating | IP65 | ||
Pressure resistance | 2.0 MPa | |||
Applied pressure range | 1.0 MPa or less | |||
Ambient temperature | 0 to +50 °C (No freezing) | |||
Relative humidity | 35 to 85 % RH (No condensation) | |||
Vibration resistance | 10 to 55 Hz, Double amplitude 1.5 mm, 2 hours in each of the X, Y, and Z directions | |||
Material | Liquid end materials | Bore : SCS13, Measurement pipe : PPS, O ring : fluoro-rubber (FKM) | ||
Material properties | Other parts | Plastic case areas : PPS, Metal case areas : SUS430, Cable : PVC | ||
Accessories | Instruction manual | |||
Weight | Approx. 835 g | |||
*1 The rated flow range indicates the range that is supposed to be used in general. |