Main controller Relay output type GC-1000R

GC-1000R - Main controller Relay output type

*Please note that accessories depicted in the image are for illustrative purposes only and may not be included with the product.

Data Sheet (PDF)

Manuals

CAD Data

360°view (3D PDF)

Software

  • CE Marking
  • UL Listing(c/us)
  • CSA

Specifications

Model

GC-1000R

Input/output points

Safety inputs

14

Safety outputs

4

Safety relay output

1 (3a)

AUX outputs

4

Test outputs

Maximum number of connectable expansion units

Maximum number of connectable remote I/O modules

GC-Link ports

2 ports

Safety input specifications

Input device

Contact output device or PNP output device

Input type

Type3

ON level (voltage/current)

Min. 11 V/2 mA

OFF level (voltage/current)

Max. 5 V/1.5 mA

Short-circuit current

Si 0 to 3: Approx. 5 mA
Si 4 to 13: Approx. 3 mA

Protection circuit

Surge protection circuit, wrong wiring protection circuit

Maximum cable length

Max. 100 m

Safety output specifications

Output type

PNP transistor output (DC-13, Type 0.5, Protected outputs) *1

Maximum load current

500 mA

Residual voltage (during ON)

Max. 2.0 V

Leakage current (during OFF)

Max. 0.5mA

Maximum capacitive load

0.5 μF

Load wiring resistance

Max. 2.5Ω

Protection circuit

Overcurrent protection circuit, reverse connection protection circuit

Maximum cable length

Max. 30 m

Safety relay output specifications

Output type

Relay (3a) (Externally-protected outputs) *2

Rated load (resistance load)

250 VAC 6A / 30 VDC 6A *3

Rated load (inductive load)

240 VAC 2A (AC-15) / 24 VDC 1A (DC-13)

Relay output mechanical life

Resistance load (250 VAC 6A/30 VDC 6A): Min. 100,000 times
Resistance load (250 VAC 1A/30 VDC 1 A): Min. 500,000 times
Inductive load (AC-15: 240 VAC 2 A): Min. 100,000 times (cosø = 0.3)
Inductive load (DC-13: 24 VDC 1 A): Min. 100,000 times (L/R = 48 ms)

Maximum cable length

Max. 100 m

B10d

With rated load: 400,000 times
With low load: 2,000,000 times

Test output specifications

Output type

PNP transistor output *4

Maximum load current

100 mA

Protection circuit

Overcurrent protection circuit, reverse connection protection circuit

Maximum cable length

Max. 100 m *5

AUX output specifications

Output type

Transistor output (PNP/NPN selectable by wiring)
PNP output (DC-13, Type 0.1, Protected outputs) *1 *4

Maximum load current

PNP: 100 mA, NPN: 20 mA

Residual voltage (during ON)

Max. 2.0 V

Leakage current (during OFF)

Max. 0.5 mA

Protection circuit

Overcurrent protection circuit, reverse connection protection circuit

Maximum cable length

Max. 30 m

Communication interface

USB

USB2.0

Ethernet

Network functionality

Others

LCD display

1.77-inch colour LCD

Display buttons

4 points (3 operation keys + 1 BACK key)

Applicable standards

EMC

EMS: IEC 61131-2/-6, EN61131-2/-6
EMI: IEC 61131-2, FCC Part15B Class A,
ICES-003, Class A

Safety

IEC 61508,EN61508 SIL3
ISO/EN13849-1:2015 Cat. 4, PL e

Dimensions

85×95×90 mm (W×D×H)

Power supply

Power voltage

24 VDC (-20 to +20%) Class 2

Current consumption

Max. 200 mA

Environmental resistance

Ambient temperature

−10 to +55 °C (No freezing)

Storage temperature

−25 to +70 °C (No freezing)

Relative humidity

5 to 85% (No condensation)

Operating altitude

Max. 2000 m

Overvoltage category

II
III (relay output part of GC-1000R and GC-S1R)

Pollution degree

2

Vibration resistance

Frequency: 5 to 9 Hz, Half amplitude: 3.5 mm
Frequency: 9 to 150 Hz, Acceleration: 10 m/s2
10 times each in X, Y, Z directions

Shock resistance

Acceleration: 150 m/s2, Operating time: 11 ms, 3 times each in X, Y, Z directions

Material

Polycarbonate

Weight

Approx. 360 g

*1 Paragraph 6.4.6 Temporary overload of IEC 61131-2 supports up to 1.2 times the maximum load current.
*2 To comply with the requirements of IEC61131-2, connect 10 A fast blow fuse (IEC 60217) in series to each contact.
*3 Check the derating characteristics described later.
*4 AUX outputs (NPN output) and test outputs do not comply with paragraph 6.4.6 of IEC 61131-2.
*5 When the test output is branched and connected to multiple safety input devices, the total branched cable length must not exceed 400 m.

Data Sheet (PDF) Other Models